![ABB RELION RET670 Скачать руководство пользователя страница 496](http://html.mh-extra.com/html/abb/relion-ret670/relion-ret670_applications-manual_4714496.webp)
tSOTF
: the drop delay of ZCVPSOF is, by default, set to 1.0 seconds, which is suitable
for most applications.
tDLD
: The time delay for activating ZCVPSOF by the internal dead-line detection is,
by default, set to 0.2 seconds. It is suitable in most applications. The delay shall not be
set too short to avoid unwanted activations during transients in the system.
Mode
: The operation of ZCVPSOF has three modes for defining the criteria for
tripping. The setting of
Mode
is, by default,
UILevel
, which means that the tripping
criterion is based on the setting of
IPh<
and
UPh<
. The choice of
UILevel
gives a
faster and more sensitive operation of the function, which is important for reducing the
stress that might occur when energizing onto a fault. However, the voltage recovery
can be slow in some systems when energizing the line. Therefore, if the timer
tDuration
is set too short, ZCVPSOF can interpret this as a fault and release a trip.
When
Mode
is set to
Impedance
, the operate criterion is based on the
BC
input (breaker
closing), which can be the start of the overreaching zone from the impedance zone
measurement or a
tOperate
-delayed
START_DLYD
input. A nondirectional output
signal should be used from an overreaching zone. The selection of the
Impedance
mode gives increased security.
When
Mode
is set to
UILvl&Imp
, the condition for tripping is an ORed between
UILevel
and
Impedance
.
tDuration
: The setting of the timer for the release of UILevel is, by default, 0.02
seconds, which has proven to be suitable in most cases from field experience. If a
shorter time delay is to be set, it is necessary to consider the voltage recovery time
during line energization.
tOperate
: The time delay for the
START_DLYD
input to activate
TRIP
when
Mode
is
set to
Impedance
or
UILvl&Imp
is, by default, set to 0.03 seconds.
8.19
Phase preference logic PPLPHIZ
SEMOD151920-1 v2
8.19.1
Identification
SEMOD151937-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase preference logic
PPLPHIZ
-
-
Section 8
1MRK 504 163-UUS A
Impedance protection
490
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...