24.12
Test mode functionality TESTMODE
IP1647-1 v3
24.12.1
Application
M11407-3 v8
The protection and control IEDs may have a complex configuration with many
included functions. To make the testing procedure easier, the IEDs include the feature
that allows individual blocking of a single-, several-, or all functions.
This means that it is possible to see when a function is activated or trips. It also enables
the user to follow the operation of several related functions to check correct
functionality and to check parts of the configuration, and so on.
24.12.1.1
IEC 61850 protocol test mode
GUID-82998715-6F23-4CAF-92E4-05E1A863CF33 v3
The IEC 61850 Test Mode has improved testing capabilities for IEC 61850 systems.
Operator commands sent to the IEC 61850 Mod determine the behavior of the
functions. The command can be given from the LHMI under the
Main menu/Test/
Function test modes
menu or remotely from an IEC 61850 client. The possible values
of IEC 61850 Mod are described in
Communication protocol manual, IEC 61850
Edition 1
and
Edition 2
.
To be able to set the IEC 61850 Mod the parameter remotely, the PST
setting
RemoteModControl
may not be set to
Off
. The possible values
are
Off
,
Maintenance
or
All levels
. The
Off
value denies all access to
data object Mod from remote,
Maintenance
requires that the category
of the originator (orCat) is
Maintenance
and
All levels
allow any orCat.
The mod of the Root LD.LNN0 can be configured under
Main menu/Test/Function
test modes/Communication/Station communication/IEC61850 LD0 LLN0/
LD0LLN0:1
When the Mod is changed at this level, all components under the logical device update
their own behavior according to IEC 61850-7-4. The supported values of IEC 61850
Mod are described in
Communication protocol manual, IEC 61850 Edition 2
. The IEC
61850 test mode is indicated with the Start LED on the LHMI.
The mod of an specific component can be configured under
Main menu/Test/
Function test modes/Communication/Station Communication
It is possible that the behavior is also influenced by other sources as well, independent
of the mode, such as the insertion of the test handle, loss of SV, and IED configuration
Section 24
1MRK 504 163-UUS A
Basic IED functions
976
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...