Operate
Angle1(2)
Power1(2)
P
Q
en06000440.vsd
IEC06000440 V1 EN-US
Figure 288:
Overpower mode
The setting
Power1(2)
gives the power component pick up value in the
Angle1(2)
direction. The setting is given in p.u. of the generator rated power, see equation
.
Minimum recommended setting is 0.2% of S
N
when metering class CT inputs into the
IED are used.
N
S
3 VBase IBase
=
×
×
EQUATION2047 V1 EN-US
(Equation 475)
The setting
Angle1(2)
gives the characteristic angle giving maximum sensitivity of the
power protection function. The setting is given in degrees. For active power the set
angle should be 0° or 180°. 180° should be used for generator reverse power
protection.
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
589
Application manual