I3PW1CT1: Phase currents for winding 1 first current transformer set.
I3PW1CT2: Phase currents for winding1 second current transformer set for multi-
breaker arrangements. When not required configure input to "GRP-OFF".
I3PW2CT1: Phase currents for winding 2 first current transformer set. Used for
autotransformers.
I3PW2CT2: Phase currents for winding 2 second current transformer set for multi-
breaker arrangements. Used when protecting an autotransformer. When not required,
configure input to "GRP-OFF".
Recommendation for Binary input signals
M13052-17 v8
Refer to the pre-configured configurations for details.
BLOCK: The input will block the operation of the function. It can be used, for
example, to block the operation during special service conditions for a limited time.
Recommendation for output signals
M13052-21 v9
Refer to pre-configured configurations for details.
PICKUP: The pickup output indicates that
Idiff
is in the operate region of the
characteristic.
TRIP: The trip output is activated when all operating criteria are fulfilled.
DIR_INT: The output is activated when the directional criteria has been fulfilled.
BLK2H: The output is activated when the function is blocked due to high level of
second harmonic.
7.3.3.2
Settings
M13052-28 v13
The parameters for the restricted earth fault protection, low impedance function
REFPDIF (87N) are set via the local HMI or PCM600.
Common base IED values for primary current (
IBase
), primary voltage (
VBase
) and
primary power (
SBase
) are set in a Global base values for settings function GBASVAL.
GlobalBaseSel
: It is used to select a GBASVAL function for reference of base values.
Operation
: The operation of REFPDIF (87N) can be switched
Enabled
/
Disabled
.
IdMin
: The setting gives the minimum operation value. The setting is in percent of the
IBase
value of the chosen
GlobalBaseSel
. For function operation, the neutral current
must be larger than half of this value. A recommended setting is 30% of power
transformer-winding rated current for a solidly grounded winding.
1MRK 504 163-UUS A
Section 7
Differential protection
Transformer protection RET670 2.2 ANSI
183
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...