R
X
IEC08000437.vsd
IEC08000437 V1 EN-US
Figure 166:
Rotation of load characteristic for a fault between two phases
This rotation may seem a bit awkward, but there is a gain in selectivity by using the
same measurement as for the quadrilateral characteristic since not all phase-to-phase
loops will be fully affected by a fault between two phases. It should also provide better
fault resistive coverage in quadrant 1. The relative loss of fault resistive coverage in
quadrant 4 should not be a problem even for applications on series compensated lines.
8.10.3
Load encroachment characteristics
GUID-DD9A62C3-A56D-411B-8303-6F7BC4C6092D v1
The phase selector must at least cover the overreaching zone 2 in order to achieve
correct phase selection for utilizing single-phase autoreclosing for faults on the entire
line. It is not necessary to cover all distance protection zones. A safety margin of at
least 10% is recommended. In order to get operation from distance zones, the phase
selection output PHSELZ or PHSELI must be connected to input PHSEL on distance
zones.
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
351
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...