Busbar
Protection
Busbar
1
2
2
1
en06000196_ansi.vsd
ANSI06000196 V1 EN-US
Figure 12:
Example how to set CT_WyePoint parameters in the IED
For busbar protection, it is possible to set the
CT_WyePoint
parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT
inputs marked with 1 in Figure
CT_WyePoint
=
ToObject
, and for all CT inputs
marked with 2 in Figure
, set
CT_WyePoint
=
FromObject
.
The second solution will be to use all connected bays as reference objects. In that case
for all CT inputs marked with 1 in Figure
CT_WyePoint
=
FromObject
, and for
all CT inputs marked with 2 in Figure
CT_WyePoint
=
ToObject
.
Section 4
1MRK 504 163-UUS A
Analog inputs
74
Transformer protection RET670 2.2 ANSI
Application manual