Figure 224:
Measured impedance at voltage inversion
Forward direction:
Where
X
LLoc
equals line reactance up to the series capacitor(in the picture
approximate 33% of XLine)
X1
Fw
is set to (XLine-X
C
) · p/100.
X1
Rv
= max( 1.5 x (X
C
-X
LLOC
C);
X1
Fw
is defined according to figure
When the calculation of
X1Fw
gives a negative value the zone 1 must be
permanently blocked.