![ABB RELION RET670 Скачать руководство пользователя страница 325](http://html.mh-extra.com/html/abb/relion-ret670/relion-ret670_applications-manual_4714325.webp)
max
3
S
ILoad
VLmn
=
×
EQUATION1615-ANSI V1 EN-US
(Equation 195)
where:
Smax
is the maximal apparent power transfer during emergency conditions and
VLmn
is the phase-to-phase voltage during the emergency conditions at the IED location.
8.8.3.1
Load encroachment
SEMOD154782-39 v4
The load encroachment function has two setting parameters,
RLd
for the load
resistance and
LdAngle
for the inclination of the load sector (see figure
).
R
X
RLdFw
RLdRv
LdAngle
LdAngle
LdAngle
ANSI10000192_1_en.vsd
LdAngle
ANSI10000192 V1 EN-US
Figure 149:
Load encroachment characteristic
The calculation of the apparent load impedance Z
load
and minimum load impedance
Z
loadmin
can be done according to equations:
min
max
3 I
V
Zload
=
×
EQUATION1754-ANSI V1 EN-US
(Equation 196)
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
319
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...