Z
A
=Z
AT
+ ·Z
TF
I
A
+ I
C
I
A
DOCUMENT11524-IMG3509 V3 EN-US
(Equation 50)
A
C
2
C
Trf
CT
TB
C
I
I
V2
Z
Z
(Z
Z ) (
)
V1
I
+
=
+
+
×
×
EQUATION1714 V1 EN-US
(Equation 51)
Where:
ZAT and ZCT
is the line impedance from the B respective C station to the T point.
IA and IC
is fault current from A respective C station for fault between T and B.
V2/V1
Transformation ratio for transformation of impedance at V1 side of the transformer to
the measuring side V2 (it is assumed that current and voltage distance function is
taken from V2 side of the transformer).
For this example with a fault between T and B, the measured impedance from the T
point to the fault can be increased by a factor defined as the sum of the currents from T
point to the fault divided by the IED current. For the IED at C, the impedance on the
high voltage side V1 has to be transferred to the measuring voltage level by the
transformer ratio.
Another complication that might occur depending on the topology is that the current
from one end can have a reverse direction for fault on the protected line. For example,
for faults at T the current from B might go in reverse direction from B to C depending
on the system parameters (as shown in the dotted line in figure
distance protection in B to T will measure wrong direction.
In three-end application, depending on the source impedance behind the IEDs, the
impedances of the protected object and the fault location, it might be necessary to
accept zone2 trip in one end or sequential trip in one end.
Generally for this type of application it is difficult to select settings of zone1 that both
gives overlapping of the zones with enough sensitivity without interference with other
zone1 settings that is, without selectivity conflicts. Careful fault calculations are
necessary to determine suitable settings and selection of proper scheme
communication.
Fault resistance
SEMOD168232-289 v2
The performance of distance protection for single phase-to-ground faults is very
important, because normally more than 70% of the faults on transmission lines are
Section 8
1MRK 504 163-UUS A
Impedance protection
204
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...