VGenZeroDb
: Minimum level of voltage in % of VBase, used as indication of zero
voltage (zero point clamping). If measured value is below
VGenZeroDb
calculated S, P,
Q and PF will be zero.
IGenZeroDb
: Minimum level of current in % of
IBase
, used as indication of zero
current (zero point clamping). If measured value is below
IGenZeroDb
calculated S, P,
Q and PF will be zero.
VMagCompY
: Magnitude compensation to calibrate voltage measurements at Y% of
Vn, where Y is equal to 5, 30 or 100.
IMagCompY
: Magnitude compensation to calibrate current measurements at Y% of In,
where Y is equal to 5, 30 or 100.
IAngCompY
: Angle compensation to calibrate angle measurements at Y% of In, where
Y is equal to 5, 30 or 100.
The following general settings can be set for the
Phase current measurement
(CMMXU).
IMagCompY
: Magnitude compensation to calibrate current measurements at Y% of In,
where Y is equal to 5, 30 or 100.
IAngCompY
: Angle compensation to calibrate angle measurements at Y% of In, where
Y is equal to 5, 30 or 100.
The following general settings can be set for the
Phase-phase voltage measurement
(VMMXU).
VMagCompY
: Amplitude compensation to calibrate voltage measurements at Y% of
Vn, where Y is equal to 5, 30 or 100.
VAngCompY
: Angle compensation to calibrate angle measurements at Y% of Vn,
where Y is equal to 5, 30 or 100.
The following general settings can be set for
all monitored quantities
included in the
functions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X in
setting names below equals S, P, Q, PF, V, I, F, IA,IB,IC, VA, VB, VCVAB, VBC,
VCA, I1, I2, 3I0, V1, V2 or 3V0.
Xmin
: Minimum value for analog signal X set directly in applicable measuring unit.
This forms the minimum limit of the range.
Xmax
: Maximum value for analog signal X. This forms the maximum limit of the
range.
XZeroDb
: Zero point clamping. A signal value less than
XZeroDb
is forced to zero.
1MRK 504 163-UUS A
Section 18
Monitoring
Transformer protection RET670 2.2 ANSI
867
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...