The PHASORREPORT filtering window is designed to receive updated input every 0.9
ms and therefore the application will fail.
Rule 2:
The same SMAI or 3PHSUM block can be connected to more than one
PHASORREPORT block only if all the connected PHASORREPORT blocks have
similar instance number or only if all the connected PHASORREPORT blocks have
similar settings for SvcClass and ReportRate. Figure
PMUREPORT function block demonstrated by PCM600 Parameter Setting Tool
(PST).
IEC140000126-2-en.vsd
IEC140000126 V2 EN-US
Figure 41:
PMUREPORT settings in PCM600 PST
shows an example of correct connection of SMAI and PHASORREPORT
blocks in ACT where two different SMAI blocks are connected to different
PHASORREPORT blocks with different instance numbers. In this example, as the
PHASORREPORT blocks have different instance numbers and different settings for
SvcClass and ReportRate, a separate SMAI block is used for each PHASORREPORT
block.
Section 6
1MRK 504 163-UUS A
Wide area measurement system
124
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...