Where
I
j
is the capacitive ground fault current at a non-resistive phase-to-ground fault
X
c
is the capacitive reactance to ground
In a system with a neutral point resistor (resistance grounded system) the impedance Z
0
can be calculated as:
c
n
0
c
n
jX 3R
Z
jX
3R
-
×
=
-
+
EQUATION1946 V1 EN-US
(Equation 438)
Where
R
n
is the resistance of the neutral point resistor
In many systems there is also a neutral point reactor (Petersen coil) connected to one or
more transformer neutral points. In such a system the impedance Z
0
can be calculated
as:
(
)
n
n
c
0
c
n
n
n
c
n
n
c
9R X X
Z
jX // 3R // j3X
3X X
j3R
3X
X
= -
=
+
×
-
EQUATION1947 V1 EN-US
(Equation 439)
Where
X
n
is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 3X
n
= X
c
In this
case the impedance Z
0
will be: Z
0
= 3R
n
Now consider a system with an grounding via a resistor giving higher ground fault
current than the high impedance grounding. The series impedances in the system can
no longer be neglected. The system with a single phase to ground fault can be
described as in Figure
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
559
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...