Figure 249:
A typical cross-country fault situation
3V
0
V
A
VB
VC
V
B
F
V
C
F
V
C
F
en06000551_ansi.vsd
ANSI06000551 V1 EN-US
Figure 250:
Voltage distribution before and during a single phase-to-ground fault
During a cross-country fault, the fault current path for the fault that is not on the
protected feeder will not go through the relay. (For a more meshed network though,
there will be some current.) See Figure
. Only in the one phase with the fault on the
protected feeder, a significant fault current may be measured by the relay. The result is
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
497
Application manual