ROADir
is Relay Operating Angle.
ROADir
is identifying a window around the
reference direction in order to detect directionality.
ROADir
is set in degrees. For
angles differing more than
ROADir
from
RCADir
the function is blocked. The setting
can be used to prevent unwanted operation for non-faulted feeders, with large
capacitive ground fault current contributions, due to CT phase angle error.
INCosPhiPU
is the pickup current level for the directional function when
OpModeSel
is set
3I0Cosfi
. The setting is given in % of
IBase
. The setting should be based on
calculation of the active or capacitive ground fault current at required sensitivity of the
protection.
SN_PU
is the pickup power level for the directional function when
OpModeSel
is set
3I03V0Cosfi
. The setting is given in % of
SBase
. The setting should be based on
calculation of the active or capacitive ground fault residual power at required
sensitivity of the protection.
The input transformer for the Sensitive directional residual over current and power
protection function has the same short circuit capacity as the phase current
transformers. Hence, there is no specific requirement for the external CT core, i.e. any
CT core can be used.
If the time delay for residual power is chosen the delay time is dependent on two
setting parameters.
SRef
is the reference residual power, given in % of
SBase
.
TDSN
is
the time multiplier. The time delay will follow the following expression:
inv
0
0
TDSN Sref
t
3I 3V cos (measured)
×
=
×
×
j
EQUATION2030-ANSI V1 EN-US
(Equation 448)
INDirPU
is the pickup current level for the directional function when
OpModeSel
is set
3I0 and fi
. The setting is given in % of
IBase
. The setting should be based on
calculation of the ground fault current at required sensitivity of the protection.
OpINNonDir
is set
Enabled
to activate the non-directional residual current protection.
INNonDirPU
is the pickup current level for the non-directional function. The setting is
given in % of
IBase
. This function can be used for detection and clearance of cross-
country faults in a shorter time than for the directional function. The current setting
should be larger than the maximum single-phase residual current on the protected line.
TimeChar
is the selection of time delay characteristic for the non-directional residual
current protection. Definite time delay and different types of inverse time
characteristics are available:
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
565
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...