IEC06000548_2_en.vsd
IED
B
A
E
B
E
A
X’
d
X
T
Z
S
Zone 1
Zone 2
jX
R
ZB
ZA
Pole slip
impedance
movement
Zone 2
Zone 1
WarnAngle
TripAngle
f
ZC
IEC06000548 V2 EN-US
Figure 236:
Settings for the Pole slip detection function
The
ImpedanceZA
is the forward impedance as show in figure
.
ZA
should be the
sum of the transformer impedance XT and the equivalent impedance of the external
system ZS. The impedance is given in % of the base impedance, according to
equation
3
Base
UBase
Z
IBase
=
EQUATION1883 V1 EN-US
(Equation 394)
Section 8
1MRK 504 163-UUS A
Impedance protection
470
Transformer protection RET670 2.2 ANSI
Application manual