11
11
<
<
+
C
S
X
X
X
X
EQUATION1898 V1 EN-US
(Equation 72)
and in figure
a three phase fault occurs beyond the capacitor. The resultant IED impedance seen
from the D
B
IED location to the fault may become negative (voltage inversion) until
the spark gap has flashed.
Distance protections of adjacent power lines shown in figure
are influenced by this
negative impedance. If the intermediate infeed of short circuit power by other lines is
taken into consideration, the negative voltage drop on X
C
is amplified and a protection
far away from the faulty line can maloperate by its instantaneous operating distance
zone, if no precaution is taken. Impedances seen by distance IEDs on adjacent power
lines are presented by equations
.
1
2
3
= +
+
I
I
I
I
EQUATION1915 V1 EN-US
(Equation 73)
X
X
I
I
X
X
DA
A
F
A
C
1
1
1
11
=
+
⋅
−
(
)
EQUATION1916 V2 EN-US
(Equation 74)
X
X
I
I
X
X
DA
A
F
A
C
2
2
2
11
=
+
⋅
−
(
)
EQUATION1917 V2 EN-US
(Equation 75)
X
X
I
I
X
X
DA
A
F
A
C
3
3
3
11
=
+
⋅
−
(
)
EQUATION1918 V2 EN-US
(Equation 76)
Section 8
1MRK 504 163-UUS A
Impedance protection
230
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...