In some applications, for instance cable lines, the angle of the loop might be less than
60°. In these applications, the settings of fault resistance coverage in forward and
reverse direction,
RFltFwdPG
and
RFltRevPG
for phase-to-ground faults and
RFltRevPP
and
RFltRevPP
for phase-to-phase faults have to be increased to avoid that
FDPSPDIS (21) characteristic shall cut off some part of the zone characteristic. The
necessary increased setting of the fault resistance coverage can be derived from
trigonometric evaluation of the basic characteristic for respectively fault type.
Phase-to-ground fault in forward direction
M13142-6 v7
With reference to figure
, the following equations for the setting calculations can be
obtained.
Index PHS in images and equations reference settings for Phase
selection with load encroachment function FDPSPDIS (21) and index
Zm reference settings for Distance protection function (ZMQPDIS, 21).
Section 8
1MRK 504 163-UUS A
Impedance protection
250
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...