t
1
tMin
D
=
EQUATION1848 V2 EN-US
(Equation 506)
Where:
DA
absolute voltage deviation from the set point
D
relative voltage deviation in respect to set deadband value
For the last equation, the condition
t1 > tMin
shall also be fulfilled. This practically
means that
tMin
will be equal to the set
t1
value when absolute voltage deviation DA is
equal to ΔV ( relative voltage deviation D is equal to 1). For other values see
figure
. It should be noted that operating times, shown in the figure
60, 90, 120, 150 & 180 seconds settings for
t1
and 10 seconds for
tMin
.
t1=180
t1=150
t1=120
t1=90
t1=60
t1=30
IEC06000488_2_en.vsd
IEC06000488 V2 EN-US
Figure 364:
Inverse time characteristic for TR1ATCC (90) and TR8ATCC (90)
The second time delay,
t2
, will be used for consecutive commands (commands in the
same direction as the first command). It can have a definite or inverse time
characteristic according to the setting
t2Use
(Constant/Inverse). Inverse time
characteristic for the second time delay follows the similar formulas as for the first
time delay, but the
t2
setting is used instead of
t1
.
1MRK 504 163-UUS A
Section 15
Control
Transformer protection RET670 2.2 ANSI
761
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...