These signals from each line bay (ABC_LINE, 3) except that of the own bay are
needed:
Signal
789OPTR
789 is open
VP789TR
The switch status for 789 is valid.
EXDU_BPB
No transmission error from the bay that contains the above information.
For bay n, these conditions are valid:
AND
BB7_D_OP
VP_BB7_D
EXDU_BPB
en04000477_ansi.vsd
AND
AND
789OPTR (bay 1)
789OPTR (bay 2)
. . .
. . .
789OPTR (bay n-1)
VP789TR (bay 1)
VP789TR (bay 2)
. . .
. . .
VP789TR (bay n-1)
EXDU_BPB (bay 1)
EXDU_BPB (bay 2)
. . .
. . .
EXDU_BPB (bay n-1)
ANSI04000477 V1 EN-US
Figure 324:
Signals from bypass busbar in line bay n
15.3.2.3
Signals from bus-coupler
M13560-31 v4
If the busbar is divided by bus-section disconnectors into bus sections, the busbar-
busbar connection could exist via the bus-section disconnector and bus-coupler within
the other bus section.
Section 15
1MRK 504 163-UUS A
Control
720
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...