![ABB RELION RET670 Скачать руководство пользователя страница 576](http://html.mh-extra.com/html/abb/relion-ret670/relion-ret670_applications-manual_4714576.webp)
If the transformer has forced cooling (FOA) the measurement should be made both
with and without the forced cooling in operation, giving
Tau2
and
Tau1
.
The time constants can be changed if the current is higher than a set value or lower
than a set value. If the current is high it is assumed that the forced cooling is activated
while it is deactivated at low current. The setting of the parameters below enables
automatic adjustment of the time constant.
Tau1High
: Multiplication factor to adjust the time constant
Tau1
if the current is higher
than the set value
IHighTau1
.
IHighTau1
is set in % of
IBase1
.
Tau1Low
: Multiplication factor to adjust the time constant
Tau1
if the current is lower
than the set value
ILowTau1
.
ILowTau1
is set in % of
IBase1
.
Tau2High
: Multiplication factor to adjust the time constant
Tau2
if the current is higher
than the set value
IHighTau2
.
IHighTau2
is set in % of
IBase2
.
Tau2Low
: Multiplication factor to adjust the time constant
Tau2
if the current is lower
than the set value
ILowTau2
.
ILowTau2
is set in % of
IBase2
.
The possibility to change time constant with the current value as the base can be useful
in different applications. Below some examples are given:
•
In case a total interruption (low current) of the protected transformer all cooling
possibilities will be inactive. This can result in a changed value of the time
constant.
•
If other components (motors) are included in the thermal protection, there is a risk
of overheating of that equipment in case of very high current. The thermal time
constant is often smaller for a motor than for the transformer.
ITrip:
The steady state current that the transformer can withstand. The setting is given
in % of
IBase1
or
IBase2
.
Alarm1
: Heat content level for activation of the signal ALARM1. ALARM1 is set in %
of the trip heat content level.
Alarm2
: Heat content level for activation of the output signal ALARM2. ALARM2 is
set in % of the trip heat content level.
LockoutReset
: Lockout release level of heat content to release the lockout signal. When
the thermal overload protection trips a lock-out signal is activated. This signal is
intended to block switching on of the protected circuit transformer as long as the
transformer temperature is high. The signal is released when the estimated heat content
is below the set value. This temperature value should be chosen below the alarm
temperature.
LockoutReset
is set in % of the trip heat content level.
Section 9
1MRK 504 163-UUS A
Current protection
570
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...