The CR signal should be configured to the functional input which provides the logic
with information on received carrier signal sent by the remote end power swing
distance protection zone.
The CS functional output signal should be configured to either output relay or to
corresponding input of the “Binary signal transfer to remote end” function.
The BLKZMPS output signal should be configured to BLOCK input of the power
swing distance protection zones.
The TRIP signal should be connected correspondingly towards the tripping
functionality of the complete distance protection within the IED.
Setting calculations
SEMOD131360-29 v1
Time delay of power swing carrier send distance protection zones
SEMOD131360-32 v2
Time delay for the underreaching or overreaching carrier send power swing zone
should be set shorter (with sufficient margin) than the time delay of normal distance
protection zone 2 to obtain selective time grading also in cases of faults during power
swings. The necessary time difference depends mostly on the speed of the
communication channel used, speed of the circuit breaker used, etc. Time difference
between 100 ms and 150 ms is generally sufficient.
Reactive reach setting of power swing distance protection zones
SEMOD131360-37 v2
Set the reactive reach for the power swing zones according to the system selectivity
planning. The reach of the underreaching zone should not exceed 85% of the protected
line length. The reach of the overreaching zone should be at least 120% of the
protected line length.
Resistive reach setting of carrier send power swing distance protection zone
SEMOD131360-40 v2
Determine the minimum possible speed of impedance Δ
Z
/ Δ
t
in primary Ω /
s
of the
expected power swings. When better information is not available from system studies,
the following equation may be used:
min
min
2
z
L
s
v
Z
f
= ×
×
EQUATION1537 V1 EN-US
(Equation 390)
Where:
v
z
is a minimum expected speed of swing impedance in Ω /
s
Z
Lmin
is a minimum expected primary load impedance in Ω
f
smin
is a minimum expected oscillation (swing) frequency in
Hz
Calculate the maximum permissible resistive reach for each power swing zone
separately according to the following equations.
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
463
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...