MultPU
: The set operate current can be changed by activation of the binary input
MULTPU to the set factor
MultPU
.
9.1.3.1
Meshed network without parallel line
M12915-9 v8
The following fault calculations have to be done for three-phase, single-phase-to-
ground and two-phase-to-ground faults. With reference to Figure
, apply a fault in
B and then calculate the current through-fault phase current I
fB
. The calculation should
be done using the minimum source impedance values for Z
A
and the maximum source
impedance values for Z
B
in order to get the maximum through fault current from A to
B.
~
~
Z
A
Z
B
Z
L
A
B
IED
I
fB
Fault
ANSI09000022-1-en.vsd
ANSI09000022 V1 EN-US
Figure 256:
Through fault current from A to B: I
fB
Then a fault in A has to be applied and the through fault current I
fA
has to be
calculated, Figure
. In order to get the maximum through fault current, the
minimum value for Z
B
and the maximum value for Z
A
have to be considered.
1MRK 504 163-UUS A
Section 9
Current protection
Transformer protection RET670 2.2 ANSI
515
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...