transformer winding or connection. This will block all trips by the distance protection
since they are based on voltage measurement.
In the pilot channel blocking scheme a fault inception detected by a fast acting change
detector is used to send a block signal to the remote end in order to block an
overreaching zone. If the fault is later detected as a forward fault the earlier sent
blocking signal is stopped.
The blocking scheme is very dependable because it will operate for faults anywhere on
the protected line if the communication channel is out of service. Conversely, it is less
secure than permissive schemes because it will trip for external faults within the reach
of the tripping function if the communication channel is out of service. Inadequate
speed or dependability can cause spurious tripping for external faults. Inadequate
security can cause delayed tripping for internal faults.
ZSMGAPC function also includes functionality for blocking the sample based distance
protection due to high SIR. SIR directly influences the fault voltage level for a given
voltage level, and this is the major factor that affects the severity of CVT transients.
Therefore, in cases where the SIR value is too high, further filtering of the measured
signals will be needed.
8.7.3
Setting guidelines
SEMOD174968-1 v1
SEMOD154558-7 v4
GlobalBaseSel
: Selects the global base value group used by the function to define
IBase
,
VBase
and
SBase
as applicable.
PilotMode
: Set
PilotMode
to
On
when pilot scheme is to be used. In this mode fault
inception function will send a block signal to remote end to block the overreaching
zones, when operated.
DeltaI
: The setting of
DeltaI
for fault inception detection is by default set to 10% of
IBase
, which is suitable in most cases.
Delta3I0
: The setting of the parameter
Delta3I0
for fault inception detection is by
default set to 10% of
VBase
, which is suitable in most cases.
DeltaV
: The setting of
DeltaV
for fault inception detection is by default set to 5% of
IBase
, which is suitable in most cases.
Delta3V0
: The setting of
Delta3V0
for fault inception detection is by default set to 5%
of
VBase
, which is suitable in most cases.
Zreach
: The setting of
Zreach
must be adopted to the specific application. The setting
is used in the SIR calculation for detection of high SIR.
Section 8
1MRK 504 163-UUS A
Impedance protection
316
Transformer protection RET670 2.2 ANSI
Application manual
Содержание RELION RET670
Страница 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Application manual ...
Страница 2: ......
Страница 48: ...42 ...
Страница 64: ...58 ...
Страница 74: ...68 ...
Страница 104: ...98 ...
Страница 194: ...188 ...
Страница 518: ...512 ...
Страница 618: ...612 ...
Страница 648: ...642 ...
Страница 666: ...660 ...
Страница 672: ...666 ...
Страница 682: ...676 ...
Страница 844: ...838 ...
Страница 868: ...862 ...
Страница 956: ...950 ...
Страница 964: ...958 ...
Страница 1004: ...998 ...
Страница 1014: ...1008 ...
Страница 1015: ...1009 ...