where:
RFPP
Zm
is the setting of the longest reach of the overreaching zones that must be covered by
FRPSPDIS (21).
Equation
are is also valid for three-phase fault. The proposed margin of
25% will cater for the risk of cut off of the zone measuring characteristic that might
occur at three-phase fault when FRPSPDIS (21)characteristic angle is changed from 60
degrees to 90 degrees or from 70 degrees to 100 degrees (rotated 30° anti-clock wise).
Section 8
1MRK 504 163-UUS A
Impedance protection
356