triggered with zone 2 pickup,
Z2pick up
enumeration has to be selected . If zone 3
select
Z3pick up
enumeration.
27_COMP
: The pickup value of the under voltage seal-in feature can be set using
27_COMP
. This is provided in percentage of
VBase
. Recommended setting is 70%.
timeDelay27
: The operate time delay in seconds for the under voltage seal-in. The
recommended time delay is to provide the same trip delay setting as the selected zone
that is, either zone 2 or zone 3.
1MRK 504 163-UUS A
Section 8
Impedance protection
Transformer protection RET670 2.2 ANSI
511
Application manual