Page D-5
FIGURE D-11: CLUTCH CONNECTIONS ASTERN SOLENOID
G) Position the Control Head lever into the Astern
detent. The measurement should be 12 or 24 VDC
depending on the Astern Solenoid’s rating. The
LED adjacent to the Astern plug on the Break-out
Box should be lit. Return the Control Head lever
to the Neutral/Idle position.
Procedures: Troll Testing
Troll On/Off Solenoid
A) Ensure power is removed from both the Processor
and the Clutch Power Supply.
B) Disconnect the Clutch Harness from the number
3 Processor connector/pigtail.
C) Insert the Break-out Box between the number 3
Processor connector/pigtail and the Clutch
Harness as shown in Figure D-12.
FIGURE D-12: TROLL CONNECTIONS TROLL ON/OFF
SOLENOID
D) Set up the Multimeter to measure DC Volts and
connect the black lead to the socket labeled
“CLUTCH –” and the red lead to the socket
labeled “TROLL ON/OFF” as shown in Figure D-
12.
E) Turn power ‘On’ to the Processor and the Clutch
Power Supply and take command at a Remote
Station with the Control Head lever in the
Neutral/Idle position.
F) Depress the Transfer Button again for
approximately 2 seconds until the red LED begins
blinking at a fast rate (Troll Mode Indication).
G) The measurement should be 0 VDC.
H) Position the Control Head lever to the Ahead
detent. The measurement should now be 12 or 24
VDC, depending on the Solenoid’s rating.
I) Position the Control Head lever further forward
while monitoring the DC Voltmeter. The
measurement should go from 12 or 24 VDC to 0
VDC at the same time the red LED on the Control
Head becomes lit solid.
Troll Command
(Proportional Solenoid)
Testing with Amp Meter
A) Ensure power is removed from both the Processor
and the Clutch Power Supply.
B) Disconnect the Clutch Harness from the number
3 Processor connector/pigtail.
C) Insert the Break-out Box between the number 3
Processor connector/pigtail and the Clutch
Harness as shown in Figure D-13.
FIGURE D-13: TROLL CONNECTIONS (PROPORTIONAL
SOLENOID)
D) Set up the Multimeter to measure (mA.) and
connect the black lead to black socket and the red
lead to the red socket labeled “TROLL
COMMAND” as shown in Figure D-13.
E) Turn power ‘On’ to the Processor and the Clutch
Power Supply and take command at a Remote
Station with the Control Head lever in the
Neutral/Idle position.
F) Depress the Transfer Button again for
approximately 2 seconds until the red LED on the
Control Head begins blinking at a fast rate (Troll
Mode Indication).
G) Flip switch away from “Troll Command” to read
current through meter.
H) Move the Control Head lever to the Ahead detent.
The current measurement should be the correct
value for minimum clutch pressure (shaft
rotations). This value varies depending on the
type of Marine Gear. Refer to the Literature
provided with the Trolling Valve and the
Processor for specifics.
I) Slowly advance the Control Head lever while
monitoring the current. The current should
increase or decrease, depending on the Gear type,
in proportion with the Control Head lever
movement. Once again, refer to the Literature
provided with the Trolling Valve and the
Processor for specific values.
J) Continue to move the Control Head lever forward
until the red LED stops blinking (lit steady). The
current should drop to 0 mA.
Summary of Contents for ClearCommand 9000 Series
Page 132: ......
Page 133: ...APPENDIX A...
Page 134: ......
Page 139: ......
Page 140: ...Page A 4...
Page 143: ......
Page 144: ...10...
Page 148: ...Page A 18...
Page 149: ...Page A 19 TEMPLATE...
Page 150: ...Page A 20...
Page 152: ...Page A 22...
Page 154: ...Page A 24...
Page 156: ...Page A 26...
Page 157: ...Page A 27 Drawing 11488D 1 Twin Screw Single APS Connection Alternate Remote Switch...
Page 158: ...Page A 28...
Page 159: ...Page A 29 Drawing 11488D 2 Twin Screw Dual APS Connections...
Page 160: ...Page A 30...
Page 161: ...Page A 31 Drawing 11488D 3 APS Notes Page...
Page 162: ...Page A 32...
Page 164: ...Page A 34...
Page 166: ...Page A 36...
Page 170: ...Page A 40...
Page 172: ...Page A 42...
Page 176: ...Page A 46...
Page 178: ...Page C 48 ZF Mathers LLC 12125 Harbour Reach Drive Suite B Mukilteo WA 98275...
Page 179: ...APPENDIX B...
Page 180: ......
Page 234: ...Appendix B 6...
Page 238: ...Appendix B 10...
Page 242: ...Appendix B 14...
Page 247: ...Service Field Test Unit Reference Manual MM13927 Rev E 4 07...
Page 248: ......
Page 250: ...Page ii Table of Contents...
Page 264: ...SERVICE FIELD TEST UNIT MM13927 RvD 10 03 Page 3 2...
Page 265: ...APPENDIX C...
Page 266: ......
Page 267: ...Appendix C 1 Drawing 12284A 1 ClearCommand Diagram all options...
Page 268: ...Appendix C 2...
Page 269: ...Appendix C 3 Drawing 12284A 2 ClearCommand Circuit Board Connections...
Page 270: ...Appendix C 4...
Page 271: ...Appendix C 5 Drawing 12284A 3 ClearCommand Drawing Notes Page...
Page 272: ...Appendix C 6...