TROUBLESHOOTING
Page B6-1
B6 TROUBLESHOOTING STATION TRANSFER
In order to transfer command from one Remote Station to another,
the following must occur:
•
There must be a valid “Command Signal” at the Station being
transferred to.
• The “Command Signal” must indicate that the Control Head’s
lever(s) is at the Neutral/Idle position.
• The Transfer Button must be depressed which takes the “Station
Select” signal from 5.00 VDC to 0.00 VDC.
If a transfer from one Remote Station to another is requested, but
does not take place; the items required for successful transfer can
be tested as follows:
B6-1 C
OMMAND
S
IGNAL
The Command Signal is a DC voltage which varies in relationship
to the Control Head’s lever position.
The Processor provides each Control Head 5.00 +/- 0.20VDC,
which is referred to as the “Reference Voltage”.
The Reference Voltage is applied to a 5K Ohm Potentiometer in the
Control Head.
The potentiometer’s “Wiper” taps off a portion of the Reference
Voltage and sends it back to the Processor.
The amount of DC voltage which is tapped off, is dependant on the
position of the Control Head’s lever.
When the lever is fully Astern, a small portion of the Reference
Voltage is tapped off by the wiper, and therefore, the volt-
age is at its lowest point (approximately 0.80 VDC).
When the lever is positioned fully Ahead, a larger portion is tapped
off and the voltage is at its highest point (approximately
4.10 VDC).
B6-2 A
TO
D C
OUNTS
Since all the calculations within the control system are performed
digitally, these DC voltages are expressed as and converted to a dig-
ital representation.
• The “Reference Voltage” (approximately 5.00 VDC) by which all
analog inputs are based, is represented as 1023 A/D (Analog to
Digital) Counts.
• This allows for the possibility of a 1024 possible positions when 0
is included in the count.
• The value of the Command Voltage with the lever at the Neutral/
Idle position is 49- 51% of the Reference Voltage when measured
at the Station terminal block. The actual value read by the Proces-
sor is 2% below that value or 47% to 49% of 1023 A/D Counts (485-
505 A/D).
Summary of Contents for ClearCommand 9000 Series
Page 132: ......
Page 133: ...APPENDIX A...
Page 134: ......
Page 139: ......
Page 140: ...Page A 4...
Page 143: ......
Page 144: ...10...
Page 148: ...Page A 18...
Page 149: ...Page A 19 TEMPLATE...
Page 150: ...Page A 20...
Page 152: ...Page A 22...
Page 154: ...Page A 24...
Page 156: ...Page A 26...
Page 157: ...Page A 27 Drawing 11488D 1 Twin Screw Single APS Connection Alternate Remote Switch...
Page 158: ...Page A 28...
Page 159: ...Page A 29 Drawing 11488D 2 Twin Screw Dual APS Connections...
Page 160: ...Page A 30...
Page 161: ...Page A 31 Drawing 11488D 3 APS Notes Page...
Page 162: ...Page A 32...
Page 164: ...Page A 34...
Page 166: ...Page A 36...
Page 170: ...Page A 40...
Page 172: ...Page A 42...
Page 176: ...Page A 46...
Page 178: ...Page C 48 ZF Mathers LLC 12125 Harbour Reach Drive Suite B Mukilteo WA 98275...
Page 179: ...APPENDIX B...
Page 180: ......
Page 234: ...Appendix B 6...
Page 238: ...Appendix B 10...
Page 242: ...Appendix B 14...
Page 247: ...Service Field Test Unit Reference Manual MM13927 Rev E 4 07...
Page 248: ......
Page 250: ...Page ii Table of Contents...
Page 264: ...SERVICE FIELD TEST UNIT MM13927 RvD 10 03 Page 3 2...
Page 265: ...APPENDIX C...
Page 266: ......
Page 267: ...Appendix C 1 Drawing 12284A 1 ClearCommand Diagram all options...
Page 268: ...Appendix C 2...
Page 269: ...Appendix C 3 Drawing 12284A 2 ClearCommand Circuit Board Connections...
Page 270: ...Appendix C 4...
Page 271: ...Appendix C 5 Drawing 12284A 3 ClearCommand Drawing Notes Page...
Page 272: ...Appendix C 6...