DK40i Installation
AC Power and Grounding Requirements
3-4
Strata DK I&M 6/00
AC Power and Grounding Requirements
The DK40i requires a solid earth ground for proper operation.
The AC power cord contains a conductor
for the “third-wire ground” provided by
the commercial power outlet. The third-
wire ground should be the only ground
necessary for the DK40i; this ground
must originate at the buildings main
power distribution panel and have a solid
connection to earth ground. (See
CAUTION!
Lack of proper ground
may cause improper
operation and, in extreme
cases, system failure.
AC Power and Third-wire Ground Test
Test the “third-wire ground” for continuity by either measuring the resistance between the third
prong terminal (earth ground) and a metal cold water pipe (maximum: 1 ohm), or by using a
commercially available earth ground indicator. If neither procedure is possible, perform the
following earth ground test procedure.
➤
To perform the earth ground test procedure
1. Obtain a suitable voltmeter, and set it for a possible reading of up to 250VAC.
2. Connect the meter probes between the two main AC voltage terminals (white and black wires)
on the wall outlet. The reading obtained should be between 100~125VAC.
3. Move one of the meter probes to the third terminal (green wire ground). Either the same
reading or a reading of zero volts should be obtained.
4. If the reading is zero volts, leave one probe on the ground terminal and move the other probe
to the second voltage terminal.
CAUTION!
If a reading of zero volts is obtained on both voltage terminals (white wire to
green wire, black wire to green wire), the outlet is not properly grounded. Omit
Steps 5 and 6, and see following CAUTION!
5. If a reading of zero volts on one terminal, and a reading of 100~125VAC on the other terminal
is obtained, remove both probes from the outlet.
WARNING!
Hazardous voltages that may cause death or injury are exposed during the
following test. Use great care when working with AC power line voltage.
Figure 3-3
DK40i Grounding Diagram
Power
Supply
FG
Third Wire
AC Ground
Ground 1
Third Wire Ground
To AC Power Cord
DK40i Base KSU
A
Electrical Building
Ground (Main Power
Distribution Box)
Alternate Ground
Grounding Rod
AC Voltage
115VAC
± 10VAC
AC Current
1.8 amps max.
4236
4' 5"
Summary of Contents for Strata AirLink DK40i
Page 22: ...Introduction Related Documents Media xx Strata DK I M 6 00 ...
Page 48: ...DK14 Installation DK14 Wiring Diagrams 1 26 Strata DK I M 6 00 ...
Page 220: ...DK424 Installation Remote Cabinet Installation Instructions 5 68 Strata DK I M 6 00 ...
Page 262: ...DK424i Configuration Primary Reserve Power Cabinet Hardware 6 42 Strata DK I M 6 00 ...
Page 450: ...Universal Slot PCB Wiring Option Interface PCB Wiring Diagrams 10 42 Strata DK I M 6 00 ...
Page 592: ...Peripheral Installation Enhanced 911 Service E911 12 84 Strata DK I M 6 00 ...
Page 616: ...ACD Installation Spectrum Electronic Wall Boards 13 24 Strata DK I M 6 00 ...
Page 634: ...Fault Finding Fault Isolation Flowcharts 14 18 Strata DK I M 6 00 ...
Page 704: ...ISDN Interfaces ISDN Disconnect Cause Code 16 54 Strata DK I M 6 00 ...