Step 4: Install AC Power Components
7-22
Strata DK I&M 6/00
Cabinet AC Power Considerations
The Strata DK424i power supply works with either 120VAC, 208VAC or 240VAC. The first
release of Strata DK424i only requires 120VAC (up to three cabinets if one AC cord is allowed or
five cabinets if two AC cords are allowed – see below).
In the future, the system will support more than five cabinets. In the case where system has more
then five cabinets, 208VAC or 240AVC is required for the primary AC power source. 208VAC or
240VAC can always be optionally used for systems with five or less cabinets for future growth or,
if the electrical code requires.
To determine AC power requirements, it is necessary to check local electrical code requirements
for 120VAC, 208VAC or 240VAC primary power. Some electrical codes stipulate that:
♦
208VAC or 240VAC is required for telephones systems
♦
Only one electrical cord can connect to the telephone system.
♦
Only two electrical cords can connect to the telephone system.
♦
No electrical cord can connect to the telephone system – must use conduit wiring installed by
a certified electrician (example: when system is floor mounted).
Cabinet AC Power Component Configuration
show the cabinet parts required to distribute AC power for various
configurations of the DK424i cabinets.
show how to install these parts.
Primary AC power components required for Wall Mounted systems.
Important!
The plugs and wall receptacles required by the local electrical code might differ for
208VAC and 240VAC. Thus in some areas of the U.S., the plug used on the Toshiba
240VAC power strip and 240VAC power supply cord (NEMA code 6-20P) can not
be used for 208VAC installations. In this case, when using 208VAC, the AC plugs on
the BPSB240 power strip cord that connects directly to the 208VAC wall outlet must
be changed by a certified electrician per the local electrical code.
Table 7-5
Wall Mount Cabinet Power Component Requirements for 120VAC Primary Power
Local Electrical Code
1 Cabinet
2 Cabinets
3 Cabinets
4 Cabinets
5 Cabinets
Allows only one 120VAC
power cord from system
0 RPSB2
1 RPSB2
1 RPSB2
N/A
N/A
Allows two 120VAC power
cords from system
0 RPSB2
0 RPSB2
1 RPSB2
1 RPSB2
2 RPSB2
●
One dedicated, isolated, 20 amp. AC circuit breaker with dual outlets is required.
●
N/A= If the system contains more than three cabinets and if the local code allows only one AC cord, the system requires
a BCCB120 conduit box wired by a certified electrician when using 120VAC as primary power. Otherwise, 208VAC or
240VAC should be used as the primary power source (see cabinet power options listed below).
Table 7-6
Wall Mount Cabinet Power Component Requirements for 208VAC or
240VAC Primary Power
Local Electrical Code
1 Cabinet
2 Cabinets
3 Cabinets
4 Cabinets
5 Cabinets
Allows One AC power cord
from system
1 BACL240
1 BPSB240
2 BACL240
1 BPSB240
3 BACL240
2 BPSB240
4 BACL240
2 BPSB240
5 BACL240
Summary of Contents for Strata AirLink DK40i
Page 22: ...Introduction Related Documents Media xx Strata DK I M 6 00 ...
Page 48: ...DK14 Installation DK14 Wiring Diagrams 1 26 Strata DK I M 6 00 ...
Page 220: ...DK424 Installation Remote Cabinet Installation Instructions 5 68 Strata DK I M 6 00 ...
Page 262: ...DK424i Configuration Primary Reserve Power Cabinet Hardware 6 42 Strata DK I M 6 00 ...
Page 450: ...Universal Slot PCB Wiring Option Interface PCB Wiring Diagrams 10 42 Strata DK I M 6 00 ...
Page 592: ...Peripheral Installation Enhanced 911 Service E911 12 84 Strata DK I M 6 00 ...
Page 616: ...ACD Installation Spectrum Electronic Wall Boards 13 24 Strata DK I M 6 00 ...
Page 634: ...Fault Finding Fault Isolation Flowcharts 14 18 Strata DK I M 6 00 ...
Page 704: ...ISDN Interfaces ISDN Disconnect Cause Code 16 54 Strata DK I M 6 00 ...