Teledyne API T/E-Series Models 101, 102, and 108 Software Documentation (PN05492D DCN6485)
A-26
Signal Name
Bit or Channel
Number
Description
6–7
Always
1
Control outputs, U17, J1008, pins 1–8 = bits 0–7, default I/O address 321 hex
0–7
Spare
Control outputs, U21, J1008, pins 9–12 = bits 0–3, default I/O address 325 hex
0–3
Spare
Alarm outputs, U21, J1009, pins 1–12 = bits 4–7, default I/O address 325 hex
ST_SYSTEM_OK2
4
1 = system OK
0 = any alarm condition or in diagnostics mode
ST_CONC_ALARM_1
5
5
1 = conc. limit 1 exceeded
0 = conc. OK
ST_CONC_ALARM_2
5
6
1 = conc. limit 2 exceeded
0 = conc. OK
ST_HIGH_RANGE2
6
7
1 = high auto-range in use (mirrors
ST_HIGH_RANGE
status output)
0 = low auto-range
A status outputs, U24, J1017, pins 1–8 = bits 0–7, default I/O address 323 hex
ST_SYSTEM_OK
0
0 = system OK
1 = any alarm condition
ST_CONC_VALID
1
0 = conc. valid
1 = warnings or other conditions that affect validity
of concentration
ST_HIGH_RANGE
2
0 = high auto-range in use
1 = low auto-range
ST_ZERO_CAL
3
0 = in zero calibration
1 = not in zero
ST_SPAN_CAL
4
0 = in span calibration
1 = not in span
ST_DIAG_MODE
5
0 = in diagnostic mode
1 = not in diagnostic mode
ST_H2S_MODE
6
0 = secondary gas mode (H2S/TRS)
1 = primary gas mode (SO2)
ST_TRS_MODE
3
7
0 = TRS gas mode
1 = primary gas mode (SO2)
B status outputs, U27, J1018, pins 1–8 = bits 0–7, default I/O address 324 hex
ST_LAMP_ALARM
0
0 = lamp intensity low
1 = lamp intensity OK
ST_DARK_CAL_ALARM
1
0 = dark cal. warning
1 = dark cal. OK
ST_FLOW_ALARM
2
0 = any flow alarm
1 = all flows OK
ST_PRESS_ALARM
3
0 = any pressure alarm
07266B DCN6485
Summary of Contents for T101
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...ii This page intentionally left blank ...
Page 10: ...vi This page intentionally left blank ...
Page 12: ...viii This page intentionally left blank ...
Page 22: ...TABLE OF CONTENTS Teledyne ML T101 Operation Manual xviii This page intentionally left blank ...
Page 166: ...Remote Operation Teledyne ML T101 Operation Manual 162 This page intentionally left blank ...
Page 248: ......
Page 336: ...This page intentionally left blank B 4 07266B DCN6485 ...
Page 339: ...APPENDIX D Wire List and Electronic Schematics D 1 07266B DCN6485 ...
Page 340: ...This page intentionally left blank 07266B DCN6485 D 2 ...
Page 345: ...D 7 07266B DCN6485 ...