2.5 Emergency Overcurrent Protection
89
7ST6 Manual
E50417-G1176-C251-A3
I Emerg. O/C
In address
2705
you specify the pickup threshold
I Emerg. O/C
of the emergency
overcurrent protection.
When using a personal computer and DIGSI
®
to apply the settings, these can be op-
tionally entered as primary or secondary values. If secondary quantities are used, all
currents must be converted to the secondary side of the current transformers.
The dropout to pickup ratio of the stage is 0.95.
T Emerg. O/C
In address
2706
you set the delay time
T Emerg. O/C
of the emergency overcurrent
protection.
The set times are pure additional delays which do not include the inherent operating
time of the protection.
2.5.4
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.5.5
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2303
Inrush O/C BU
NO
YES
NO
Emerg. O/C Blocked by
Inrush
2701
Emerg. O/C
ON
OFF
ON
Emergency Overcurrent
Function
2702
SOTF Emerg. O/C
NO
YES
NO
Instantan. trip after Switch-
onto-Fault
2705
I Emerg. O/C
1A
0.10 .. 25.00 A;
∞
2.00 A
Emergency O/C Pickup
Current
5A
0.50 .. 125.00 A;
∞
10.00 A
2706
T Emerg. O/C
0.00 .. 30.00 sec;
∞
0.30 sec
Emergency O/C Delay
Time
No.
Information
Type of In-
formation
Comments
2001
>Emer. ON
SP
>Switch ON emerg. overcurrent prot.
2002
>Emer. OFF
SP
>Switch OFF emerg. overcurrent prot.
2051
Emer. off
OUT
Emergency O/C protect. is switched off
2053
Emer. active
OUT
Emergency O/C protection is active
2061
Emer.Gen.Flt
OUT
Emerg. O/C prot.: General fault detect.
2141
Emer.Gen.Trip
OUT
Emerg. O/C protection: General Trip
13842
Emer. Rush blk
OUT
Emerg. O/C Protection: Inrush blocked
13994
Emer. ON/OFF BI
IntSP
Emerg.O/C Prot.: ON/OFF via Binary Input