4.15 User Defined Functions (CFC) (optional)
283
7ST6 Manual
E50417-G1176-C251-A3
Maximum Number of TICKS in the Task Levels
1)
When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error indication
is output by CFC.
Processing Times in TICKS Required by the Individual Elements
Task Level
Limit in TICKS
MW_BEARB (Measured value processing)
10 000
PLC1_BEARB (Slow PLC processing)
1 900
PLC_BEARB (Fast PLC processing)
200
SFS_BEARB (Switchgear interlocking)
10 000
Individual Element
Number of TICKS
Block, basic requirement
5
Each input more than 3 inputs for generic modules
1
Combination with input signal border
6
Combination with output signal border
7
Additionally for each chart
1
Operating sequence module
CMD_CHAIN
34
Flip-flop
D_FF_MEMO
6
Loop module
LOOP
8
Decoder
DM_DECODE
8
Dynamic OR
DYN_OR
6
Addition
ADD
26
Subtraction
SUB
26
Multiplication
MUL
26
Division
DIV
54
Square root
SQUARE_ROOT
83