2 Functions
108
7ST6 Manual
E50417-G1176-C251-A3
2.8.3
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
2.8.4
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
3901
FCT BreakerFail
ON
OFF
OFF
Breaker Failure Protection
is
3902
I> BF
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold I>
5A
0.25 .. 100.00 A
0.50 A
3904
tBF1
0.10 .. 10.00 sec;
∞
0.50 sec
Delay Time Backup Trip
Element
3905
tBF2
0.10 .. 10.00 sec;
∞
0.75 sec
Delay Time Higher-Level
Protection
No.
Information
Type of In-
formation
Comments
157
Fail. MAIN CB
OUT
Failure of main circuit breaker
1401
>BF on
SP
>BF: Switch on breaker fail protection
1402
>BF off
SP
>BF: Switch off breaker fail protection
1431
>BrkFail extSRC
SP
>Breaker failure initiated externally
1440
BkrFailON/offBI
IntSP
Breaker failure prot. ON/OFF via BI
1451
BkrFail OFF
OUT
Breaker failure is switched OFF
1455
B/F fault
OUT
Breaker failure : fault detection
1471
BrkFailure TRIP
OUT
Breaker failure TRIP
1484
B/F s.ordProt
OUT
B/F: pick up superordinat.prot.relais
13998
BF T-BF1
OUT
Delay time for back up trip expired