2 Functions
138
7ST6 Manual
E50417-G1176-C251-A3
„AR no starter“
(FNo. 2823)
In the configuration parameters
AR w/ DIST.
(address
3405
),
AR w/ HS O/C
(ad-
dress
3406
),
AR w/ DTT
(address
3407
) and the parameter
AUTO-TH-AR
(address
3450
) no source has been defined for starting the auto reclose function. The automat-
ic reclosure is therefore statically blocked. With the parameter
3430
:
1.AR: START
and
3440
:
2nd Recl:START
, no start of one of the possible cycles is enabled. The
automatic reclosure is therefore statically blocked. This state can only be changed by
modification of the settings.
„AR in progress“
(FNo. 2801)
This information appears following starting of the auto reclose function, i.e. with the
first trip command that can start the auto reclose function. If this reclosure was suc-
cessful (or any in the case of more than one), this information resets with the expiry of
the last reclaim time. If no reclosure was successful or if reclosure was blocked, it ends
with the last – the final – trip command.
„AR Sync.Request“
(FNo. 2865)
Measuring request to an external synchronism check device. The information appears
at the end of a dead time subsequent to tripping if a synchronism request is present.
Reclosure only takes place when the synchronism check device has provided the
release signal
„>Sync.release“
(FNo.2731).
„>Sync.release“
(FNo. 2731)
Release of reclosure by an external synchronism check device if this was requested
by the output information
„AR Sync.Request“
(FNo. 2865).