A Appendix
318
7ST6 Manual
E50417-G1176-C251-A3
2705
I Emerg. O/C
Emerg. O/C
1A
0.10 .. 25.00 A;
∞
2.00 A
Emergency O/C Pickup Current
5A
0.50 .. 125.00 A;
∞
10.00 A
2706
T Emerg. O/C
Emerg. O/C
0.00 .. 30.00 sec;
∞
0.30 sec
Emergency O/C Delay Time
2901
MEASURE. SUPERV
Monitoring
With FFM
Without FFM
OFF
With FFM
Measurement Supervision
2921
I> CB
Trip Superv
1A
0.05 .. 0.50 A
0.10 A
Pickup Current Trip Supervision
5A
0.25 .. 2.50 A
0.50 A
2922
T I> CB MAX
Trip Superv
1 .. 200 sec
30 sec
Maximum Duration of Trip Super-
vision
3401
AUTO RECLOSE
Auto Reclose
OFF
ON
ON
Auto-Reclose Function
3402
No.Recl.
Auto Reclose
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
1 AR-cycle
Maximum Number of Reclosure
Attempts
3405
AR w/ DIST.
Auto Reclose
YES
NO
YES
AR with Distance Protection
3406
AR w/ HS O/C
Auto Reclose
YES
NO
YES
AR with HS O/C Protection
3407
AR w/ DTT
Auto Reclose
YES
NO
YES
AR with direct transfer trip
3411
I LIMIT BLK
Auto Reclose
1 .. 25 A; 0;
∞
10 A
Current Limit for AR Blocking
3412
No.Recl. HS O/C
Auto Reclose
1 AR-cycle
All AR Cycles
1 AR-cycle
No. of Reclosure Attempts HS
O/C Tripped
3413
AR BLK REVERSE
Auto Reclose
YES
NO
NO
AR Blocking at Faults Reverse
Direction
3415
CB? 1.TRIP
Auto Reclose
YES
NO
NO
CB ready interrogation at 1st trip
3416
T-Start MONITOR
Auto Reclose
0.01 .. 300.00 sec
0.50 sec
AR start-signal monitoring time
3417
CB TIME OUT
Auto Reclose
0.01 .. 300.00 sec
3.00 sec
Circuit Breaker (CB) Supervision
Time
3420
TIME RESTRAINT
Auto Reclose
0.50 .. 300.00 sec
3.00 sec
Auto Reclosing reset time
3421A
T-DEAD EXT.
Auto Reclose
0.50 .. 300.00 sec;
∞
∞
sec
Maximum dead time extension
3423
T-BLOCK MC
Auto Reclose
0.50 .. 300.00 sec; 0
1.00 sec
AR blocking duration after
manual close
3430
1.AR: START
Auto Reclose
YES
NO
YES
Start of AR allowed in this cycle
3431
1.AR: T-ACTION
Auto Reclose
0.01 .. 300.00 sec;
∞
0.20 sec
Action Time
3432
1st Recl: Tdead
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead Time for 1st Reclosure
Cycle
3434
SYN-CHECK
Auto Reclose
YES
NO
NO
Synchro-Check after Dead Time
3440
2nd Recl:START
Auto Reclose
YES
NO
NO
Start 2nd Reclosure Cycle Per-
mitted
3441
2-8 Recl:T SI
Auto Reclose
0.01 .. 300.00 sec;
∞
0.20 sec
Seal-In Time for 2nd-8th Reclo-
sure Cycle
3442
2-8 Recl:Tdead
Auto Reclose
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead Time for 2nd to 8th Reclo-
sure Cycle
3450
AUTO-TH-AR
Auto Reclose
ON
OFF
ON
Automatic Reclosure after
Thermal Trip
3451
No. of TH-AR
Auto Reclose
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
1 AR-cycle
Max. Number Automatic Reclo-
sure Attempts
3455
TInhibit TH
Auto Reclose
0.50 .. 300.00 sec
3.00 sec
Inhibit Time after Reclosure
3456
Tdead TH MAX
Auto Reclose
1 .. 60 min;
∞
30 min
Maximum Duration of Dead Time
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments