2.13 Synchronism and Voltage Check
151
7ST6 Manual
E50417-G1176-C251-A3
2.13.4 Information List
3538
MC Uref<Uline<
YES
NO
NO
Dead Ref. / Dead Line Check
before MC
3539
MC O/RIDE
YES
NO
NO
Override of any check before
Man.Cl
No.
Information
Type of In-
formation
Comments
2901
>Sync. on
SP
>Switch on synchro-check function
2902
>Sync. off
SP
>Switch off synchro-check function
2903
>BLOCK Sync.
SP
>BLOCK synchro-check function
2905
>Sync. Start MC
SP
>Start synchro-check for Manual Close
2906
>Sync. Start AR
SP
>Start synchro-check for AR
2907
>Sync. synch
SP
>Sync-Prog. Live bus / live line / Sync
2911
>Sync. o/ride
SP
>Sync-Prog. Override ( bypass )
2930
Sync. on/off BI
IntSP
Synchro-check ON/OFF via BI
2931
Sync. OFF
OUT
Synchro-check is switched OFF
2932
Sync. BLOCK
OUT
Synchro-check is BLOCKED
2934
Sync. faulty
OUT
Synchro-check function faulty
2935
Sync.Tsup.Exp
OUT
Synchro-check supervision time expired
2936
Sync. req.CNTRL
OUT
Synchro-check request by control
2941
Sync. running
OUT
Synchronization is running
2942
Sync.Override
OUT
Synchro-check override/bypass
2943
Synchronism
OUT
Synchronism detected
2944
SYN Uref<Uline>
OUT
Sync. Dead ref. / Live line detected
2945
SYN Uref>Uline<
OUT
Sync. Live ref. / Dead line detected
2946
SYN Uref<Uline<
OUT
Sync. Dead ref. / Dead line detected
2947
Sync. Udiff>
OUT
Sync. Voltage diff. greater than limit
2948
Sync. fdiff>
OUT
Sync. Freq. diff. greater than limit
2949
Sync.
ϕ
-diff>
OUT
Sync. Angle diff. greater than limit
2951
Sync. release
OUT
Synchronism release (to ext. AR)
2961
Sync.CloseCmd
OUT
Close command from synchro-check
2970
Sync. fref>>
OUT
Sync. Reference frequency > (fn+3Hz)
2971
Sync. fref<<
OUT
Sync. Reference frequency < (fn-3Hz)
2972
Sync. f-line>>
OUT
Sync. Line frequency > (fn + 3Hz)
2973
Sync. f-line<<
OUT
Sync. Line frequency < (fn - 3Hz)
2974
Sync. Uref>>
OUT
Sync. Reference voltage > Umax
2975
Sync. Uref<<
OUT
Sync. Reference voltage < U>
2976
Sync. U-line>>
OUT
Sync. Line voltage > Umax (P.3504)
2977
Sync. U-line<<
OUT
Sync. Line voltage < U> (P.3503)
Addr.
Parameter
Setting Options
Default Setting
Comments