2 Functions
150
7ST6 Manual
E50417-G1176-C251-A3
2.13.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr.
Parameter
Setting Options
Default Setting
Comments
3501
FCT Synchronism
ON
OFF
ON
Synchronism and Voltage Check
function
3502
Dead Volt. Thr.
1 .. 60 V
5 V
Voltage Threshold Dead Line /
Reference
3503
Live Volt. Thr.
20 .. 125 V
90 V
Voltage Threshold Live Line / Ref-
erence
3504
Umax
20 .. 140 V
110 V
Maximum permissible voltage
3507
T-SYN. DURATION
0.01 .. 600.00 sec;
∞
1.00 sec
Maximum duration of synchro-
nism-check
3508
T SYNC-STAB
0.00 .. 30.00 sec
0.00 sec
Synchronous condition stability
timer
3509
SyncSD
(Setting options depend
on configuration)
None
synchronizable switching device
3510
Op.mode with AR
with T-CB close
w/o T-CB close
w/o T-CB close
Operating mode with AR
3511
Max. Volt. Diff
1.0 .. 50.0 V
2.0 V
Maximum voltage difference
3512
Max. Freq. Diff
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency difference
3513
Max. Angle Diff
1 .. 80
°
10
°
Maximum angle difference
3515A
SYNC-CHECK
YES
NO
YES
Live Ref. / Live Line and Sync
3516
Uref>Uline<
YES
NO
NO
Live Ref. / Dead Line Check
3517
Uref<Uline>
YES
NO
NO
Dead Ref. / Live Line Check
3518
Uref<Uline<
YES
NO
NO
Dead Ref. / Dead Line Check
3519
OVERRIDE
YES
NO
NO
Override of any check before AR
3530
Op.mode with MC
with T-CB close
w/o T-CB close
w/o T-CB close
Operating mode with Man.Cl
3531
MC maxVolt.Diff
1.0 .. 50.0 V
2.0 V
Maximum voltage difference
3532
MC maxFreq.Diff
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency difference
3533
MC maxAngleDiff
1 .. 80
°
10
°
Maximum angle difference
3535A
MC SYNCHR
YES
NO
YES
Live Ref. / Live Line and Sync
before MC
3536
MC Uref>Uline<
YES
NO
NO
Live Ref. / Dead Line Check
before MC
3537
MC Uref<Uline>
YES
NO
NO
Dead Ref. / Live Line Check
before MC
www
. ElectricalPartManuals
. com