3 Mounting and Commissioning
224
7ST6 Manual
E50417-G1176-C251-A3
C-I/O-13 Input/Out-
put Board
Figure 3-9
C-I/O-13 input/output board with representation of jumper settings required for
checking configuration settings
Table 3-16
Jumper settings of
Pickup Voltages
of the binary input BI6 on the input/output
board C-I/O-13
1)
Factory settings for devices with rated power supply voltages 24 VDC to 125 VDC
2)
Factory settings for devices with rated power supply voltages 110 VDC to 250 VDC
3)
Use only with pickup voltages 220 to 250 VDC
Jumpers X71, X72 and X73 on the input/output board C-I/O-13 are used to set the bus
address and must not be changed. The following table lists the jumper presettings.
Binary Input
Jumper Threshold 19 V
Threshold 88 V
Threshold 176 V
BI6
X21
L
M
H