2.12 Automatic Reclosure Function
139
7ST6 Manual
E50417-G1176-C251-A3
2.12.3 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr.
Parameter
Setting Options
Default Setting
Comments
3401
AUTO RECLOSE
OFF
ON
ON
Auto-Reclose Function
3402
No.Recl.
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
1 AR-cycle
Maximum Number of Reclosure
Attempts
3405
AR w/ DIST.
YES
NO
YES
AR with Distance Protection
3406
AR w/ HS O/C
YES
NO
YES
AR with HS O/C Protection
3407
AR w/ DTT
YES
NO
YES
AR with direct transfer trip
3411
I LIMIT BLK
1 .. 25 A; 0;
∞
10 A
Current Limit for AR Blocking
3412
No.Recl. HS O/C
1 AR-cycle
All AR Cycles
1 AR-cycle
No. of Reclosure Attempts HS
O/C Tripped
3413
AR BLK REVERSE
YES
NO
NO
AR Blocking at Faults Reverse Di-
rection
3415
CB? 1.TRIP
YES
NO
NO
CB ready interrogation at 1st trip
3416
T-Start MONITOR
0.01 .. 300.00 sec
0.50 sec
AR start-signal monitoring time
3417
CB TIME OUT
0.01 .. 300.00 sec
3.00 sec
Circuit Breaker (CB) Supervision
Time
3420
TIME RESTRAINT
0.50 .. 300.00 sec
3.00 sec
Auto Reclosing reset time
3421A
T-DEAD EXT.
0.50 .. 300.00 sec;
∞
∞
sec
Maximum dead time extension
3423
T-BLOCK MC
0.50 .. 300.00 sec; 0
1.00 sec
AR blocking duration after manual
close
3430
1.AR: START
YES
NO
YES
Start of AR allowed in this cycle
3431
1.AR: T-ACTION
0.01 .. 300.00 sec;
∞
0.20 sec
Action Time
3432
1st Recl: Tdead
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead Time for 1st Reclosure
Cycle
3434
SYN-CHECK
YES
NO
NO
Synchro-Check after Dead Time
3440
2nd Recl:START
YES
NO
NO
Start 2nd Reclosure Cycle Permit-
ted
3441
2-8 Recl:T SI
0.01 .. 300.00 sec;
∞
0.20 sec
Seal-In Time for 2nd-8th Reclo-
sure Cycle