2.13 Synchronism and Voltage Check
149
7ST6 Manual
E50417-G1176-C251-A3
Note
The closing functions of the device issue individual output indications for the corre-
sponding close command. Be sure that the output indications are assigned to the
correct output relays.
FNo. 2851
„AR Close“
for CLOSE via command of the automatic reclosure,
FNo. 562
„Man.Close Cmd“
for manual CLOSE via binary input,
FNo. 2961
„Sync.CloseCmd“
for CLOSE via synchronism check (not required if
synchronism check releases the other CLOSE commands),
FNo. 13864
„CB-TEST CLOSE M“
for CLOSE by circuit breaker test,
additionally CLOSE command via control, e.g.
„Breaker“
.
FNo. 510
„Relay CLOSE“
general CLOSE command for all CLOSE commands de-
scribed above.
Notes on the Infor-
mation List
The most important information of the device is briefly explained in so far as it cannot
be interpreted in the following information lists or described in detail in the foregoing
text.
„>Sync. Start MC“
(FNo. 2905)
Binary input which enables direct tripping of the synchronism check with setting pa-
rameters for manual close. This tripping with setting parameter for manual close has
always precedence if binary inputs
„>Sync. Start MC“
(FNo. 2905) and
„>Sync.
Start AR“
(FNo. 2906, see below) are activated at the same time.
„>Sync. Start AR“
(FNo. 2906)
Measuring request from an internal automatic reclosure device. After this request, the
conditions for automatic reclosure are checked.
„Sync. req.CNTRL“
(FNo. 2936)
Measuring request form the control; evaluated on event-triggered basis and output
only when the control issues a measuring request.
„Sync. release“
(FNo. 2951)
Release signal to an external automatic reclosure device.