A.5 Default Settings
303
7ST6 Manual
E50417-G1176-C251-A3
Table A-8
Further output relay presettings for 7ST63*
A.5.4
Function Keys
Table A-9
Applies to all devices and ordered variants
Binary Output
Allocated Func-
tion
Function No.
Description
BO9
Dis.Trip Z1
3810
Dist.: Trip in Zone Z1
BO10
Dis. Trip Z2K
3930
Dist.: Trip in zone Z2 (short circuit)
BO11
Dis. Trip Z2L
3931
Dist.: Trip in zone Z2 (overload)
BO12
Dis TRIP Z3K
13903
Dist. Prot. TRIP Zone Z3 (short cir-
cuit)
BO13
Dis TRIP Z3L
13904
Dist. Prot. TRIP Zone Z3 (overload)
BO15
B/F s.ordProt
1484
B/F: pick up superordinat.prot.relais
BO17
Dis. Z1 act.
3915
Dist.: Zone Z1 is active
BO18
Dis.Z1str act
3916
Dist.: Zone Z1 stroke is active
BO19
Dis.Z2 act.
3917
Dist.: Zone Z2 is active
BO20
Dis.Z2str act
3918
Dist.: Zone Z2 stroke is active
BO21
Dis. Z3 act
3991
Dist.: Zone Z3 is active
BO22
Dis. Z3str act
3992
Dist.: Zone Z3 stroke is active
BO24
Cat. 1 active
6616
First catenary is active
BO25
Cat. 2 active
6617
Second catenary is active
BO26
Cat. 3 active
6618
Third catenary is active
BO27
Relay TRIP
511
Relay GENERAL TRIP command
BO28
Relay CLOSE
510
General CLOSE of relay
BO29
O/L
Θ
Alarm
1516
Overload Alarm! Near Thermal Trip
BO30
Fail.TEMPSENS
158
Failure of outdoor temp. sensing
BO32
CB-TEST TRIP M
13862
CB-Test: TRIP command main trip
element
CB-TEST TRIP B
13863
CB-Test: TRIP command backup trip
elem.
BO33
CB-TEST CLOSE
M
13864
CB-Test: CLOSE command main trip
element
CB-TEST CLOSE B 13865
CB-Test: CLOSE command backup
trip elem.
BO37
Device OK
51
Device is Operational and Protecting
Function Keys
Allocated Func-
tion
Function No.
Description
F1
Display of Opera-
tional Indications
-
-
F2
Operating Mea-
sured Values,
Primary
-
-
F3
An overview of the
last eight network
faults
-
-
F4
Not assigned
-
-