2 Functions
180
7ST6 Manual
E50417-G1176-C251-A3
taken into consideration when configuring the protection functions (address
133
Auto
Reclose
).
This contact is also opened when closing the breaker via the binary input
„>Manual
Close“
(FNo. 356), so that no breaker alarm can pass there either.
Further optional closing commands which are not sent via the device cannot be taken
into consideration. Closing commands for control can be linked to the alarm suppres-
sion via the user-defined logic functions (CFC).
Figure 2-58
Breaker tripping alarm suppression
If the device issues a final trip command, the contact remains closed. This is the case,
during the reclaim time of the automatic reclosure cycle, when the automatic reclosure
is blocked or switched off or, due to other reasons is not ready for automatic reclosure,
e.g. tripping only occurred after the action time expired.
Figure 2-59 shows time diagrams for manual trip and close as well as for short-circuit
tripping with a single, failed automatic reclosure cycle.