4.5 Thermal Overload Protection
275
7ST6 Manual
E50417-G1176-C251-A3
4.5
Thermal Overload Protection
Setting Ranges
Dropout to Pickup Ratio
Tolerances
Factor k ITRise = ITRise / I
N
(continuous limit current) 0.10 to 4.00
Increments 0.01
Time constant TAU
2.0 min to 30.0 min
Increments 0.1 min (6 s)
Final temperature rise TRise (for continuous limit cur-
rent)
0 to 100 K
Increments 1 K
Trip temperature TEMP TRIP
50 to 100
°
C
Increments 1
°
C
Alarm temperature TEMP ALARM
40 to 100
°
C
Increments 1
°
C
Close temperature TEMP CLOSE
25 to 100
°
C
Increments 1
°
C
Factor for 2 catenaries CAT2
1.0 to 3.0
Increments 0.1
Factor for 3 catenaries CAT3
1.0 to 3.0
Increments 0.1
Fixed ambient temperature value TEMP.SENS
VALUE
-55 to 40
°
C
Increments 1
°
C
ULS TRIP
Drops out with internal signal
„Current=0“
No dropout to pickup ratio
ULS ALARM
1K (dropout threshold =
pickup value –1K)
ULS BLOCK
TEMP TRIP/TEMP CLOSE
Depends on the settings of
TEMP TRIP and TEMP
CLOSE
Currents
2 % of measured value (for currents above I
N
), or 2 % of rated
current (for currents < I
N
)
Times
3 % or 1 s
Ambient temperature
+/-1 K
www
. ElectricalPartManuals
. com