A Appendix
306
7ST6 Manual
E50417-G1176-C251-A3
A.5.6
Pre-defined CFC Charts
Some CFC charts are already supplied with the SIPROTEC 4 device. Depending on
the variant the following charts may be implemented:
Device and System
Logic
Some of the event-controlled logical allocations are created with blocks of the slow
logic (
PLC1_BEARB
= slow PLC processing). This way, the binary input „Data Stop“
is modified from a single point indication (SP) into an internal single point indication
(IntSP) by means of a negator block.
With double point indication „EarthSwit.“ = CLOSE an indication saying
„fdrEARTHED“ ON and with „EarthSwit.“ = OPEN or INT the indication „fdrEARTHED“
OFF is generated.
From the output indication „definite TRIP“ the internal indication „Brk OPENED“ is gen-
erated. As indication „definite TRIP“ is only queued for 500 ms, indication „Device Brk
OPENED“ is also reset after this time.
Figure A-10
Allocation of input and output with blocks of level System Logic