2.12 Automatic Reclosure Function
133
7ST6 Manual
E50417-G1176-C251-A3
nism and voltage check function is available or that an external device is available for
synchronism check. Where no stability problems are to be expected during the auto-
reclosure dead time, set address
3434
to
NO
.
2nd to 8th Reclo-
sure Cycle
In address
3440
2nd Recl:START
you set whether the 2nd to 8th cycle are permit-
ted to start the auto reclose function (=
YES
) or not.
If more than two cycles are set in address
3402
, those following the second cycle use
the settings of the second cycle.
The table below shows a summary of the parameters of the 2nd cycle.
Table 2-5
Auto reclose function – 2nd to 8th cycle
CB Ready Interro-
gation at 1st Trip
If the setting of address
3415
CB? 1.TRIP
=
YES
specifies that the readiness of the
circuit breaker in normal state is to be continuously monitored via the binary input 2730
„>CB Ready“
, the auto reclosure function is statically blocked if the binary input
signal drops out. The blocking is reset as soon as the binary input signal returns.
Circuit breaker ready signals that drop out during a power system fault are checked
by monitoring times.
Circuit Breaker
Open and TRIP
If the auto reclose function detects that the circuit breaker is open but that there is no
TRIP command from any internal or external protection function, the auto reclose
function is statically blocked. This state can occur, for instance, if the circuit breaker
was not actuated by the protection but by the control. A prerequisite for detection of
an open circuit breaker is in this case that the breaker auxiliary contacts are connected
to the auto reclose function. The blocking is reset when the circuit breaker is closed.
Address
Parameter
Description
3440
2nd Recl:START
Start of auto reclose permitted for 2nd to
8th cycle
3441
2-8 Recl:T SI
Action time for 2nd to 8th reclosure cycle
3442
2-8 Recl:Tdead
Dead time for 2nd to 8th reclosure cycle