4 Technical Data
278
7ST6 Manual
E50417-G1176-C251-A3
4.9
Automatic Reclosure Function (optional)
General AR Function
AR Function for Thermal Overload Protection
Number of reclosures
Max. 8,
the first 2 with individual parameters
optionally 1 with SOTF-O/C
Polarization
1-pole
Control
With TRIP Command
Action times
0.01 s to 300.00 s
2 separate parameters for cycle 1 and 2-8
Dead times prior to reclosure
0.01 s to 1800.00 s
2 separate parameters for cycle 1 and 2-8
Dead time extension - monitoring time
0.50 to 300.0 s;
∞
Reclaim time after reclosure
0.50 to 300.0 s
Blocking time after dynamic blocking
0.50 to 300.0 s
Blocking time after manual closing
0.50 to 300.0 s
Start signal monitoring time
0.01 to 300.0 s
Circuit-breaker monitoring time
0.01 to 300.0 s
I
Limit
1 to 25 A
Increments 1 A
Dynamic blocking in reverse direction
Yes/No
Number of reclosures
Max. 8
Polarization
1-pole
Control
With PU=TRIP command
Operating Time
PU=TRIP
Dead time extension monitoring time
See "General AR Function"
Dead time duration monitoring time
1 to 60 min
Reclaim time after reclosure
0.50 to 300.0 s
Blocking time after dynamic blocking
See "General AR Function"
Blocking time after manual closing
See "General AR Function"
Start signal monitoring time
See "General AR Function"
Circuit-breaker monitoring time
See "General AR Function"
I
Limit
See "General AR Function"
www