2.2 Distance Protection
71
7ST6 Manual
E50417-G1176-C251-A3
1326
R1B Reverse
1A
0.20 .. 250.00
Ω
6.00
Ω
Resistance R Zone Z1B
Reverse
5A
0.04 .. 50.00
Ω
1.20
Ω
1327
X1B Reverse
1A
0.20 .. 250.00
Ω
12.00
Ω
Reactance X Zone Z1B
Reverse
5A
0.04 .. 50.00
Ω
2.40
Ω
1328
Z1B Reverse
1A
0.20 .. 250.00
Ω
12.00
Ω
Impedance Z Zone Z1B
Reverse
5A
0.04 .. 50.00
Ω
2.40
Ω
1331
Op. Mode Z1L
Forward
Forward ext.
Reverse
Non-Directional
Inactive
Forward
Operating Mode Distance
Zone Z1L
1332
T1L
0.00 .. 60.00 sec;
∞
0.40 sec
Delay Time Zone Z1L
1333
R1L
1A
0.20 .. 250.00
Ω
9.00
Ω
Resistance R Zone Z1L
5A
0.04 .. 50.00
Ω
1.80
Ω
1334
X1L
1A
0.20 .. 250.00
Ω
18.00
Ω
Reactance X Zone Z1L
5A
0.04 .. 50.00
Ω
3.60
Ω
1335
Z1L
1A
0.20 .. 250.00
Ω
18.00
Ω
Impedance Z Zone Z1L
5A
0.04 .. 50.00
Ω
3.60
Ω
1336
R1L Reverse
1A
0.20 .. 250.00
Ω
9.00
Ω
Resistance R Zone Z1L
Reverse
5A
0.04 .. 50.00
Ω
1.80
Ω
1337
X1L Reverse
1A
0.20 .. 250.00
Ω
18.00
Ω
Reactance X Zone Z1L
Reverse
5A
0.04 .. 50.00
Ω
3.60
Ω
1338
Z1L Reverse
1A
0.20 .. 250.00
Ω
18.00
Ω
Impedance Z Zone Z1L
Reverse
5A
0.04 .. 50.00
Ω
3.60
Ω
1341
Op. Mode Z2
Forward
Forward ext.
Reverse
Non-Directional
Inactive
Forward
Operating Mode Distance
Zone Z2
1342
Zone Sel. Z2
Z active
Z Strk active
Z active
Zone Selection Zone Z2
1343
di/dt Z2
1A
0.0 .. 1.0 A;
∞
0.5 A
Pickup Value of di/dt Func-
tion Zone Z2
5A
0.0 .. 5.0 A;
∞
2.5 A
1344
du/dt Z2
0 .. 100 V;
∞
20 V
Pickup Value of du/dt
Function Zone Z2
1345
Dead VoltThr Z2
50 .. 100 V;
∞
80 V
Dead Voltage Threshold
for Zone Z2
1346
T2K
0.00 .. 30.00 sec;
∞
0.80 sec
Delay Time TK Zone Z2
1347
T2L
0.00 .. 60.00 sec;
∞
4.00 sec
Delay Time TL Zone Z2
1348
R2
1A
0.20 .. 250.00
Ω
10.00
Ω
Resistance R Zone Z2
5A
0.04 .. 50.00
Ω
2.00
Ω
Addr.
Parameter
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com