4 Technical Data
280
7ST6 Manual
E50417-G1176-C251-A3
4.11
Fault Locator (optional)
General
4.12
It Function (optional)
General
4.13
Trip Supervision
Monitoring
4.14
Trip Circuit Supervision
Trip Circuit Supervision
Start
With trip command or dropout
Reactance (secondary)
0.05 to 50.00
Ω
/km
In km or miles
Line length
1.0 to 200.0 km
Reactance (secondary)
0.08 to 80.00
Ω
/mile
Line length
0.6 to 124.0 miles
Output of the fault distance
In
Ω
primary and
Ω
secondary,
In km or miles of line length
In % of the line length
Tolerance
<3% if distance protection or time overcurrent protection trip
<6% if the high current switch on to fault protection trips
Operating mode
Start with G-Trip or start with CB auxiliary contact
Alarm stage
1.0 I/In*s to 1000 I/In*s;
∞
Statistics
Summated It
Summated I
2
t
Last It
Last I
2
t
2P
CB pickup threshold
0.05 to 0.5 A
Operating mode
With 1 binary input or with 2 binary inputs
Alarm delay
1 s to 30 s
Increments 1 s