2 Functions
72
7ST6 Manual
E50417-G1176-C251-A3
1349
X2
1A
0.20 .. 250.00
Ω
20.00
Ω
Reactance X Zone Z2
5A
0.04 .. 50.00
Ω
4.00
Ω
1350
Z2
1A
0.20 .. 250.00
Ω
20.00
Ω
Impedance Z Zone Z2
5A
0.04 .. 50.00
Ω
4.00
Ω
1351
ALPHA Z2
-70 .. 75
°
20
°
Angle Limitation Alpha
Zone Z2
1352
BETA Z2
70 .. 145
°
; 0
135
°
Angle Limitation Beta
Zone Z2
1353
GAMMA Z2
-70 .. 40
°
-20
°
Angle Limitation Gamma
Zone Z2
1354
R2 Reverse
1A
0.20 .. 250.00
Ω
10.00
Ω
Resistance R Zone Z2
Reverse
5A
0.04 .. 50.00
Ω
2.00
Ω
1355
X2 Reverse
1A
0.20 .. 250.00
Ω
20.00
Ω
Reactance X Zone Z2
Reverse
5A
0.04 .. 50.00
Ω
4.00
Ω
1356
Z2 Reverse
1A
0.20 .. 250.00
Ω
20.00
Ω
Impedance Z Zone Z2
Reverse
5A
0.04 .. 50.00
Ω
4.00
Ω
1357
X2 Strk
1A
0.20 .. 250.00
Ω
20.00
Ω
Reactance X Zone Z2
Stroke
5A
0.04 .. 50.00
Ω
4.00
Ω
1358
Z2 Strk
1A
0.20 .. 250.00
Ω
20.00
Ω
Impedance Z Zone Z2
Stroke
5A
0.04 .. 50.00
Ω
4.00
Ω
1359
X2 Strk Reverse
1A
0.20 .. 250.00
Ω
20.00
Ω
Reactance X Zone Z2
Stroke Reverse
5A
0.04 .. 50.00
Ω
4.00
Ω
1360
Z2 Strk Reverse
1A
0.20 .. 250.00
Ω
20.00
Ω
Impedance Z Zone Z2
Stroke Reverse
5A
0.04 .. 50.00
Ω
4.00
Ω
1361
Op. Mode Z3
Forward
Forward ext.
Reverse
Non-Directional
Inactive
Forward
Operating Mode Distance
Zone Z3
1362
Zone Sel. Z3
Z active
Z Strk active
Z active
Zone Selection Zone Z3
1363
di/dt Z3
1A
0.0 .. 1.0 A;
∞
0.5 A
Pickup Value of di/dt Func-
tion Zone Z3
5A
0.0 .. 5.0 A;
∞
2.5 A
1364
du/dt Z3
0 .. 100 V;
∞
20 V
Pickup Value of du/dt
Function Zone Z3
1365
Dead VoltThr Z3
50 .. 100 V;
∞
80 V
Dead Voltage Threshold
Zone Z3
1366
T3K
0.00 .. 30.00 sec;
∞
1.20 sec
Delay Time TK Zone Z3
1367
T3L
0.00 .. 60.00 sec;
∞
8.00 sec
Delay Time TL Zone Z3
1368
R3
1A
0.20 .. 250.00
Ω
15.00
Ω
Resistance R Zone Z3
5A
0.04 .. 50.00
Ω
3.00
Ω
Addr.
Parameter
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals