2.17 Trip Circuit Supervision
173
7ST6 Manual
E50417-G1176-C251-A3
2.17.2 Setting Notes
General
This function is only effective and available if address
140
Trip Cir. Sup.
has
been set to
Enabled
during configuration.
If you do not want to use the trip circuit supervision, set
Disabled
.
The trip circuit supervision can be switched
ON
or
OFF
in address
4001
FCT
TripSuperv.
.
The number of binary inputs that shall be used in each of the monitored circuits is set
in address
4002
No. of BI
. If the allocation of the required binary inputs does not
match the selected monitoring mode, a corresponding indication is issued (
„TripC1
ProgFAIL“
).
Monitoring with
One Binary Input
The alarm for monitoring with two binary inputs is always delayed by approx. 1 s to
2 s, whereas the delay time of the alarm for monitoring with one binary input can be
set in address
4003
Alarm Delay
. 1 s to 2 s are sufficient if only the 7ST6 device is
connected to the trip circuits as the trip circuit supervision does not operate during a
system fault.
If, however, trip contacts from other devices are connected in parallel in the trip circuit,
the alarm must be delayed such that the longest trip command duration can be reliably
bridged.
2.17.3 Settings
2.17.4 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
4001
FCT TripSuperv.
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
1 .. 2
2
Number of Binary Inputs per trip
circuit
4003
Alarm Delay
1 .. 30 sec
2 sec
Delay Time for alarm
No.
Information
Type of In-
formation
Comments
6854
>TripC1 TripRel
SP
>Trip circuit superv. 1: Trip Relay
6855
>TripC1 Bkr.Rel
SP
>Trip circuit superv. 1: Breaker Relay
6861
TripC OFF
OUT
Trip circuit supervision OFF
6865
FAIL: Trip cir.
OUT
Failure Trip Circuit
6866
TripC1 ProgFAIL
OUT
TripC1 blocked: Binary Input is not set